ETCR2100E+ Ground Tester Clamp Earth Resistance Tester Range 0.01-1200OHM

FOB Reference Price:Get Latest Price
$400.00 - $460.00 / Piece | 1 Piece/Pieces (Min. Order)
Lead Time:
Quantity(Pieces) 1 - 5 >5
Est. Time(days) 3 Negotiable
Report Suspicious Activity
Overview
Quick Details
Place of Origin:
Guangdong, China
Brand Name:
ETCR
Model Number:
ETCR2100E+
Display Type:
Digital Only
Measuring Current Range:
0.00mA-40.0A
Measuring Voltage Range:
/
Measuring Resistance Range:
0.01-1200OHM
Measuring Capacitance Range:
/
Measuring Inductance Range:
/
Operating Temperature:
-20c-55c;20%RH-90%RH
Dimensions:
285mm*85mm*56mm
Weight:
1160g
Supply Ability
Supply Ability:
1000 Piece/Pieces per Month
Packaging & Delivery
Packaging Details
Carton
Port
shenzhen
Lead Time :
Quantity(Pieces) 1 - 5 >5
Est. Time(days) 3 To be negotiated

 

Product Description

 

 

ETCR2100E+ Ground Tester Clamp Earth Resistance Tester Range 0.01-1200OHM

 

 

 Introduction
NEW Type 2000+ Series Clamp Earth Resistance Tester is widely applied in ground resistance measurement, loop resistance measurement in fields such as electric power, telecommunications, meteorology, oil field, architecture and industrial electrical equipment, etc. When measuring ground system with loop, there is no need to disconnect the ground wire without auxiliary electrode, which means safer and faster.
NEW Type 2000+ Series Clamp Earth Resistance Tester is another perfect upgrade on old models. 
 
Technical Specifications
FunctionGround resistance test, Loop resistance test
Power Supply6VDC 4 PCS of AA Alkaline batteries
Resistance Range0.01-1200Ω
Resistance Resolution0.001Ω
Highest Resistance Accuracy±1%±0.01Ω
Current Range0.00mA-40.0A
Current Resolution0.05mA
Highest Current Accuracy±2.5%±1mA
Data memory99 Sets
Alarm Threshold Setting RangeResistance: 1-199Ω
Alarm Sound and Light“Beep-beep-beep” alarm tone, Alarm Symbol Flashing, Press AL key to turn on, turn off Alarm or set Alarm Threshold.
Interference Signal Recognition 
“Beep-beep-beep” tone, NOISE symbol blinking
Working Temperature and Humidity-20c-55c;20%RH-90%RH
LCD Screen4 Digits LCD display, Screen L×W: 47mm×28.5mm
Clamp Size65mm×32mm
Clamp Opening Extent32mm
Tester Weight1160g (With batteries)
Clamp DimensionL×W×T: 285mm×85mm×56mm
Protection LevelDual Insulation
Structural FeatureClamp CT
ShiftingAutomatic shifting
External magnetic field<40A/m
External electrical field<1V/m
Single measurement time0.5 second
Resistance measurement frequency>1KHz
Measured current frequency50/60Hz Automatic measurement
Low Battery IndicationLow battery symbol displays when battery is lower then 5.3V
Memory Full IndicationMEM symbol blinks when all 99 sets memory is full
Over Range IndicationOut of range indication “OLΩ”, “L0.01” or “OL A”
Auto Power-off5 minutes after Boot up
Power ConsumptionMax 50mA either in booting up or normally working, Continuously working for 30 hours
RS232 Interface (Optional)The data stored in the meter are uploaded to the computer through RS232 interface and data wire, Then generate report files
Safety ProvisionsIEC1010-1  IEC1010-2-032 Pollution level 2  CAT iii(600V)
AccessoriesMeter: 1 piece, Test ring: 1 Piece, Meter Suitcase: 1 Piece
   