Display Type:
Digital Only
Measuring Range:
0.01 Mohm to 999 Gohm
Testing Voltage:
DC250V~ DC 5.00kv
Accuracy Class:
5%
Operating Temperature:
10~70°C
Dimensions:
284mm(L)*230mm(w)*125mm(H)
Supply Ability
Supply Ability:
50 Piece/Pieces per Week
Packaging & Delivery
Packaging Details
EXPORT CARTON
Port
Shenzhen
Lead Time :
Quantity(Pieces) 1 - 1 >1
Est. Time(days) 3 To be negotiated

 

YH510 High Voltage Digital Insulation Tester for Checking the Insulation of High-Voltage Electrical Equipment

 

 

  

Features:

. Checking the insulation of high-voltage electrical equipment

 (electric motor, transformer, and cable, etc)

.Test Voltage from 250V~5000V

.Insulation Resistance up to 5Tohm

. Short Current up to 3mA

. Auto Calculate PI(Polarization Index) and DAR(Dielectric absorption ratio)

. Step-Voltage Measurement

. Temperature measurement

. Temperature compensation for insulation Test

. Leakage Current measurement

. Data Storage function and uploading to PC by USB2.0 interface

. Power Supply:LR6 Battery×6/ rechargeable battery Ni~MH 7.2V

  (Charger;Input Voltage 100V~240V ; Frequency 50Hz~60Hz, Output Voltage 12V DC 3A)

. Timer Function

.Weight 2.5kg (not including Battery)

.Size 284mm(L)×230mm(w)×125mm(H)

Test Voltage:

 

. Test Voltage Range; DC250V~ DC 5.00kv

. Voltage Set:

. Wide adjust;(250V; 500V; 1000V; 2.5kv; 5kv)

. Fine adjust (250V~1KV; Step 25V; 1KV~5KV, Step 100V)

. Accuracy; 5%

. Step mode:500V, 1.0KV, 1.5KV, 2.0KV, 2.5KV

. Test Current 1nA~3mA

 

 

Temperature compensation:

 

For obtaining the insulation resistance under a temperature other than current ambient temperature.

Converts the measured value of resistance to the insulation resistance under a reference temperature, and displays the result.

Depending on the different properties of test objects, there are 10 modes of compensation.

Insulation Resistance:

 

Set test voltage 

    Test range 

Threshold value of basic error

250 V DC 

0.01 Mohm ~ 2.5 Gohm 

  ±(5% rdg + 5 dgt) 

2.51 Gohm ~ 250 Gohm 

  ±(20% rdg +10 dgt) 

500 V DC 

0.01 Mohm ~ 5.0 Gohm 

  ±(5% rdg +5 dgt) 

5.01 Gohm ~ 500 Gohm 

  ±(20% rdg +10 dgt) 

1000 V DC 

0.01 Mohm ~ 10 Gohm 

  ±(5% rdg +5 dgt) 

10.1 Gohm ~ 500 Gohm 

  ±(20% rdg +10 dgt) 

501 Gohm ~ 999 Gohm 

  ±(30% rdg +20 dgt) 

2.5 kV DC 

0.01 Mohm ~ 25 Gohm 

  ±(5% rdg +5 dgt) 

25.1 Gohm ~ 500 Gohm 

  ±(20% rdg +10 dgt) 

501 Gohm ~ 999 Gohm 

  ±(30% rdg +20 dgt) 

1 Tohm ~ 2.5 Tohm 

  ±(30% rdg + 40 dgt)

5 kV DC 

0.01 Mohm ~ 50 Gohm 

  ± (5% rdg + 5 dgt) 

50.1 Gohm ~ 500 Gohm 

  ±(20% rdg + 10 dgt)

501 Gohm ~ 999 Gohm 

  ±(30% rdg + 20 dgt)

1 Tohm ~ 5 Tohm 

  ±(30% rdg + 40 dgt)

 

 

 

 

 